AWG 线规换算
AWG 与 mm² 双向换算,附完整对照表
AWG 与 mm² 为近似对照,非精确相等;mm² → AWG 按就近匹配。以本页对照表为准。
输入参数后点击计算
AWG ↔ mm² 完整对照表 / Full Reference Table
| AWG | 直径 in | 直径 mm | 面积 kcmil | 面积 mm² | 铜电阻 Ω/km (20℃) | Ω/1000ft (20℃) | 近似 IEC mm² |
|---|---|---|---|---|---|---|---|
| 14 | 0.0641 | 1.628 | 4.11 | 2.08 | 8.286 | 2.525 | ≈2.5 |
| 12 | 0.0808 | 2.053 | 6.53 | 3.31 | 5.211 | 1.588 | ≈4 |
| 10 | 0.1019 | 2.588 | 10.4 | 5.26 | 3.277 | 0.9989 | ≈6 |
| 8 | 0.1285 | 3.264 | 16.5 | 8.37 | 2.061 | 0.6282 | ≈10 |
| 6 | 0.1620 | 4.115 | 26.3 | 13.3 | 1.296 | 0.3951 | ≈16 |
| 4 | 0.2043 | 5.189 | 41.7 | 21.2 | 0.8152 | 0.2485 | ≈25 |
| 3 | 0.2294 | 5.827 | 52.6 | 26.7 | 0.6465 | 0.1970 | — |
| 2 | 0.2576 | 6.544 | 66.4 | 33.6 | 0.5127 | 0.1563 | ≈35 |
| 1 | 0.2893 | 7.348 | 83.7 | 42.4 | 0.4066 | 0.1239 | — |
| 1/0 | 0.3249 | 8.252 | 106 | 53.5 | 0.3224 | 0.09827 | ≈50 |
| 2/0 | 0.3648 | 9.266 | 133 | 67.4 | 0.2557 | 0.07793 | ≈70 |
| 3/0 | 0.4096 | 10.404 | 168 | 85.0 | 0.2028 | 0.06180 | ≈95 |
| 4/0 | 0.4600 | 11.684 | 212 | 107 | 0.1608 | 0.04901 | ≈120 |
| 16 | — | — | — | 1.31 | — | — | ≈1.5 |
说明 / Notes:AWG(American Wire Gauge)为美国线规标准,编号越大导线越细。AWG 与 IEC mm² 系列不重合,上表“近似 IEC”为工程对照,非精确相等;选型时应以实际载流量和规范为准。直径、kcmil 与电阻列取自 calculator.net AWG 表(2026-10 抓取核对);电阻为 20℃ 直流铜阻,工作温度(约 75℃)近似 ×1.2,与本站压降口径一致。
AWG numbers run opposite to wire size: the larger the number, the thinner the wire. AWG and IEC mm² series do not align exactly — the “nearest IEC” column is an engineering approximation, not an equality.
常见问题
14 AWG 对应多少 mm²?
14 AWG 的实际截面积约 2.08 mm²,工程上近似对应 IEC 的 2.5 mm²。
AWG 数值越小线越粗吗?
是的。AWG 编号越大导线越细;本表最粗的是 4/0(0000),约 107.2 mm²,接近 IEC 的 120 mm²。
AWG 和 mm² 能直接画等号吗?
不能。两者是近似对照关系,AWG 与 IEC 线规系列并不重合。本页按 AWG 实际截面积给出近似对应,仅供参考。