短路电流计算器
Point-to-Point 法逐段估算可用故障电流,选断路器分断能力(AIC)
公式与计算依据 / Formula & Reference
Point-to-Point 公式(Bussmann):
三相 f = 1.732 × L × Isc ÷ (C × n × V);单相 f = 2 × L × Isc ÷ (C × n × V)
乘数 M = 1 ÷ (1 + f);段末 Isc = 段首 Isc × M(多段逐段相乘)
Three-phase f = 1.732 × L × Isc / (C × n × V); single-phase f = 2 × L × Isc / (C × n × V); M = 1 / (1 + f); end-of-segment Isc = start Isc × M, chained per segment.
导体常数 C(600V,铜):14 AWG=389、12=617、10=981、8=1538、6=2406、4=3806。铝导体与更大截面请查 Bussmann 手册(本工具未内置,不做插值)。
Conductor constants C (600 V, copper): 14=389, 12=617, 10=981, 8=1538, 6=2406, 4=3806. Aluminum and larger sizes: consult the Bussmann handbook (not built in, no interpolation).
变压器起点估算:FLA = kVA×1000 ÷ (√3×V);Isc = FLA ÷ (%Z÷100)。忽略上游电源阻抗,结果偏保守(偏大)。
Transformer source: FLA = kVA×1000/(√3×V); Isc = FLA/(%Z/100). Upstream impedance ignored — conservative (high) estimate.
免责 / Disclaimer:结果为简化估算,断路器 AIC 选型以正式短路计算与电力公司数据为准。
Simplified estimates only — final AIC selection requires a formal short-circuit study and utility data.
常见问题
为什么要算可用故障电流?
断路器与熔断器的分断能力(AIC)必须大于安装点的可用故障电流,否则故障时可能无法分断甚至爆裂。
什么是 point-to-point 法?
从起点故障电流出发,用导体常数 C 与阻抗逐段折减:f = 1.732·L·Isc/(C·n·V),M = 1/(1+f),段末 Isc = 段首 Isc × M。
变压器起点怎么估?
Isc ≈ 变压器满载电流 ÷ 阻抗百分数:FLA = kVA×1000/(√3×V),Isc = FLA/(%Z÷100)。本估算忽略上游电源阻抗,结果偏保守(偏大)。