电压降计算器

输入线路参数,计算电压降与压降百分比

常用 16 / 25 / 35 mm²

选择 AWG 时以此为准,忽略上方的 mm² 截面

输入参数后点击计算
公式与计算依据 / Formula & Reference

简化公式(本工具采用,只计电阻、忽略电抗):

单相:Vd = 2 × L × I × R ÷ 1000

三相:Vd = √3 × L × I × R ÷ 1000

Simplified (resistance only): single-phase Vd = 2 × L × I × R / 1000; three-phase Vd = √3 × L × I × R / 1000, where L is in m, I in A and R in Ω/km.

完整公式(供参考,含电抗项):

单相:Vd = 2 × L × I × (R·cosφ + X·sinφ) ÷ 1000

三相:Vd = √3 × L × I × (R·cosφ + X·sinφ) ÷ 1000

Full formula (with reactance): Vd = 2 (or √3) × L × I × (R·cosφ + X·sinφ) / 1000, where X ≈ 0.08 Ω/km for low-voltage cables and cosφ defaults to 0.8.

简化模型适用声明:本工具 R 取工作温度电阻,R_work = R20 × 1.2(20℃→70℃ 温升修正)。一般 120mm² 以下低压线路电阻分量占主导,简化误差可接受;大截面、长距离项目应以完整公式核算。

Scope: the simplified model ignores reactance and suits low-voltage runs up to about 120 mm² where resistance dominates. For large sections or long runs, verify with the full formula.

导体电阻表(20℃ 直流电阻,Ω/km,参考 IEC 60228):

截面 mm²1.52.54610162535507095120150185240
铜 Cu12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.0754
铝 Al20.112.17.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.125

规范参考 / References:计算方法参考 GB/T 16895 与 IEC 60364;导体电阻参考 IEC 60228;美国用户可参考 NEC Chapter 9 Table 8。压降判定限值:照明 3%、动力 5%。计算结果仅供参考,实际工程以当地规范为准。

References: GB/T 16895 and IEC 60364 for the calculation method, IEC 60228 for conductor resistance, and NEC Chapter 9 Table 8 for US users. Limits: 3% for lighting, 5% for power circuits. Results are for reference only.

常见问题

电压降超过 5% 会怎样?

压降过大时末端设备欠压运行:电机启动困难、转矩下降、灯具变暗,线路损耗和发热也会增加。建议增大导线截面、缩短供电距离或提高供电电压。

为什么三相要乘以 √3?

√3 来自线电压与相电压的关系(U 线 = √3 × U 相)。三相压降公式 Vd = √3 × L × I × R / 1000 计算的是线电压降;单相公式的系数 2 则来自往返两根导体。

单相和三相的压降公式有什么区别?

单相 Vd = 2 × L × I × R / 1000,三相 Vd = √3 × L × I × R / 1000。其余参数相同,三相系数更小,因此同等条件下三相线路压降更低。