导线选型计算器

根据负载电流推荐导线截面,并自动复核电压降

载流量为简化参考值,正式工程设计请以当地规范(GB / IEC / NEC)为准。

输入参数后点击计算
公式与计算依据 / Formula & Reference

选型逻辑:先按载流量选出最小满足截面,再用该截面复核电压降(照明 3% / 动力 5%),两步都必须满足。

Logic: pick the smallest size that meets ampacity, then verify voltage drop (3% lighting / 5% power). Both steps must pass.

载流量基准表(铜、PVC 绝缘、穿管 = 参考方法 B1、环境 30℃,单位 A,参考 IEC 60364-5-52 表 B.52.4 简化值):

截面 mm²1.52.54610162535507095120
载流量 A15.5212836506889111134171207239

修正规则(简化):铝导体载流量 = 铜的 0.78 倍;明敷(参考方法 C)= 穿管 B1 × 1.15;温度修正(空气中,PVC 70℃,基准 30℃):35℃ = 0.94、40℃ = 0.86、45℃ = 0.79、50℃ = 0.71。

Corrections: aluminum = 0.78 × copper; clipped direct (ref. method C) = B1 × 1.15; temperature factors (air, PVC 70 °C, 30 °C base): 35 °C = 0.94, 40 °C = 0.86, 45 °C = 0.79, 50 °C = 0.71.

压降复核公式(简化,只计电阻):单相 Vd = 2 × L × I × R ÷ 1000;三相 Vd = √3 × L × I × R ÷ 1000;R_work = R20 × 1.2(20℃→70℃ 温升修正)。

Drop check (simplified, resistance only): single-phase Vd = 2 × L × I × R / 1000; three-phase Vd = √3 × L × I × R / 1000, with R_work = R20 × 1.2 (20 °C → 70 °C correction).

规范参考 / References:载流量参考 IEC 60364-5-52 表 B.52.4(对应 GB/T 16895.6)、导体电阻参考 IEC 60228。载流量为简化参考值,正式工程设计请以当地规范(GB / IEC / NEC)为准。

References: IEC 60364-5-52 Table B.52.4 (GB/T 16895.6) for ampacity, IEC 60228 for conductor resistance. Ampacity values are simplified — for formal design follow local codes (GB / IEC / NEC).

常见问题

选线径先看载流量还是压降?

两者都必须满足。一般先按载流量选出最小截面,再做压降复核;长距离供电往往由压降控制,此时需要增大截面。

穿管和明敷有什么区别?

敷设方式影响散热。明敷(参考方法 C)散热更好,载流量比穿管(参考方法 B1)更高,本工具按 1.15 倍做简化处理。

铝线和铜线怎么换算?

相同截面下,铝的载流量约为铜的 0.78 倍,电阻约为铜的 1.6 倍。需要更大载流量时应增大铝线截面。