电机回路选型计算器
输入功率与电压,一次得到额定电流、导线、断路器与接触器
公式与计算依据 / Formula & Reference
额定电流(公式法,国内外通用):
三相:I = P ÷ (√3 × V × cosφ × η);单相:I = P ÷ (V × cosφ × η)
Formula: I = P / (√3 × V × pf × η) for three-phase, I = P / (V × pf × η) for single-phase. 1 HP = 0.7457 kW.
北美 NEC 查表口径(Table 430.250,三相鼠笼电机 FLC,单位 A): HP:208V / 230V / 460V / 575V 列
| HP | 208V | 230V | 460V | 575V | HP | 208V | 230V | 460V | 575V |
|---|---|---|---|---|---|---|---|---|---|
| 1/2 | 2.4 | 2.2 | 1.1 | 0.9 | 7.5 | 24.2 | 22 | 11 | 9 |
| 3/4 | 3.5 | 3.2 | 1.6 | 1.3 | 10 | 30.8 | 28 | 14 | 11 |
| 1 | 4.6 | 4.2 | 2.1 | 1.7 | 15 | 46.2 | 42 | 21 | 17 |
| 1.5 | 6.6 | 6.0 | 3.0 | 2.4 | 20 | 59.4 | 54 | 27 | 22 |
| 2 | 7.5 | 6.8 | 3.4 | 2.7 | 25 | 74.8 | 68 | 34 | 27 |
| 3 | 10.6 | 9.6 | 4.8 | 3.9 | 40 | 114 | 104 | 52 | 41 |
| 5 | 16.7 | 15.2 | 7.6 | 6.1 | 50 | 143 | 130 | 65 | 52 |
| 60 HP:169 / 154 / 77 / 62 | 75 HP:211 / 192 / 96 / 77 | ||||||||
| 200 HP:528 / 480 / 240 / 192 | 100HP 以上按铭牌 FLA 查完整表 | ||||||||
部件选型规则(北美 NEC):导线(430.22)载流量 ≥ FLC × 1.25;断路器(430.52,inverse time)≤ FLC × 2.5,允许取下一标准档(延时熔丝 ×1.75、非延时熔丝 ×3.0);过载继电器(430.32)≤ 铭牌 FLA × 1.25;接触器 AC-3 额定 ≥ FLC。启动(堵转)电流约 5–8× FLC,这是断路器需要放大的原因。北美选型一律以表内 FLC(非铭牌)为准(NEC 430.6(A)(1))。
NEC rules: conductors per 430.22 (≥ 125% of FLC), inverse-time breakers per 430.52 (≤ 250% of FLC, next standard size allowed; time-delay fuses ×1.75, non-time-delay ×3.0), overload per 430.32 (≤ 125% of nameplate FLA), contactor AC-3 ≥ FLC. Locked-rotor current is roughly 5–8× FLC. North American sizing uses table FLC, not nameplate (NEC 430.6(A)(1)).
国内简化口径:380V 三相电机额定电流经验值 ≈ 2 A/kW(功率因数与效率已含);断路器选 D 型(电动机保护型,可躲过启动冲击);以实际铭牌和 GB 规范为准。
China quick method: a 380 V three-phase motor draws about 2 A per kW; use a D-curve motor-protection breaker. Follow the nameplate and GB codes.
规范参考 / References:NEC Table 430.250 / 430.22 / 430.52 / 430.32;导线载流量为本站简化表(IEC 60364-5-52 简化值,铜穿管 B1 30℃)。计算结果仅供参考。
References: NEC Tables 430.250 / 430.22 / 430.52 / 430.32; conductor ampacity uses this site's simplified table (IEC 60364-5-52 simplified, copper in conduit B1 at 30 °C). Results are for reference only.
常见问题
电机额定电流怎么估算?
380V 三相电机可用经验值约 2 A/kW 快速估算;精确值按 I = P ÷ (√3 × U × cosφ × η) 计算,北美电机可查 NEC Table 430.250 的 FLC。
为什么电机断路器可以选到 2.5 倍?
电机启动(堵转)电流约为额定电流的 5–8 倍,断路器必须躲过启动冲击不误跳。NEC 430.52 允许反时限断路器整定到 FLC 的 250%。